§ 8-1-3-1211.2.6 — Amendment to Section 1211.2.6 of the UPC
Salina Code, City of Salina, Kansas (Codified through Ordinance No. 26-11299 adopted August 24, 2026. (Supp. No. 19)) · Salina Municipal Code § 8-1-3-1211.2.6
Corpus is an independent public-information project, not the official City of Salina website. Stable reference: corpuslaw.us/code/148e51a2-e761-4d3a-b0c0-10a4b198fd61
Sec. 8-1-3-1211.2.6. - Amendment to Section 1211.2.6 of the UPC.
Section 1211.2.6 of the UPC is amended to read as follows: Sec. 1211.2.6 Arc-Resistant Jacketed CSST. CSST listed with an arc resistant jacket or coating system in accordance with ANSI LC1/CSA 6.26, Fuel Gas Piping Systems Using Corrugated Stainless Steel Tubing, shall be electrically continuous and bonded to an effective ground fault current path.Where any CSST component of a piping system does not have an arc-resistant jacket or coating system, the bonding requirements of 1210.15.2 shall apply. Arc-resistant jacketed CSST shall be considered to be bonded when it is connected to appliances that are connected to the appliance grounding conductor of the circuit supplying that appliance.
(Ord. No. 25-11270, § 1, 12-8-25)