Sec. 8-1-3-1208.10.4. - Amendment to Section 1208.10.4 of the UPC.

Section 1208.10.4 of the UPC is amended to read as follows: Sec. 1208.10.4 Flow Capacity. If a pressure relief valve is used to meet the requirements of this section, it shall have a flow capacity such that the pressure in the protected system is maintained at or below the limits specified in Section 1208.10.2 under the following conditions: (1) The line pressure regulator for which the relief valve is providing overpressure protection has failed wide open. (2) The gas pressure at the inlet of the line pressure regulator for which the relief valve is providing overpressure protection is not less than the regulator's normal operating inlet pressure. [NFPA 54:5.9.2.5]

(Ord. No. 25-11270, § 1, 12-8-25)