24.05.200 Medium- and High-pressure Gas Piping.
(a) General. Approval of the Administrative Authority and verification from the serving gas supplier of the availability of the desired pressure shall be obtained before any medium- or high-pressure gas-piping system is installed. (b) Applicability. The following requirements shall apply to medium-pressure gas-piping systems. (c) Pressure Regulators. Approved regulators shall be installed on medium- and high-pressure gas-piping systems, in approved locations, and shall be accessible for servicing. Each regulator shall have a separate vent to the outside. EXCEPTION: Pounds-to-inches water-column regulators equipped with limiting orifices capable of releasing not more than five cubic feet of gas per hour when supplied with medium pressure need not be vented to an outside location when the regulators have been approved by the Administrative Authority. These regulators shall: (1) Be connected to the same piping material used to pipe the structure. A listed gas connector may be used to attach the low-pressure piping downstream of the regulator to the appliance manifold. (2) Have an approved gas valve in the supply line upstream of the pounds-to inches water-column regulator. (3) Be accessible. (4) Have the upstream pressure identified. Such identification shall be an approved tag permanently attached to the regulator and state: Warning 1/2 to 5 pounds natural gas pressure. DO NOT REMOVE. (5) Be installed in a ventilated area. An approved gas valve shall be installed immediately preceding each regulator. Regulators that may be subjected to mechanical damage shall be substantially protected to the satisfaction of the Administrative Authority. (d) Three or 5 psig. Tables Nos. 6 and 7 set out at the end of this chapter may be used to size a natural gas piping system carrying 3 or 5 psig gas. The procedure to determine the size of each section of the system is similar to that contained in Section 24.05.190 using the pipe length from the meter to the most remote regulator on the medium- pressure system and sizing the downstream low-pressure piping from Table No. 4 or 4A as applicable. (e) Ten psig. Table No. 8 set out at the end of this chapter may be used to size undiluted liquefied petroleum gas-piping systems carrying 10 psig gas. The procedure to determine the size of each section of the system is similar to Section 24.05.190 using the pipe length from the first stage or tank regulator to the most remote regulator in the second-stage system. Low-pressure piping shall be sized from Table No. 5A or 5B, as set out at the end of this chapter, as applicable. (f) Corrosion and Cover Protection. Buried medium pressure gas piping shall be protected from corrosion as required by Section 24.05.130 and shall have a minimum earth cover of eighteen inches. Piping shall be covered with at least six inches of hand-placed selected backfill devoid of rocks, building materials or other matter that may damage the pipe or wrapping.
(Ord. 16542 §20; January 24, 1994)
Ask a question about Lincoln law
Corpus searches the Lincoln sections it holds and shows the ones that match, with their citations. Free, no sign-in.