For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 14.05.0500 — Chapter 5—Fire service features

Code of Ordinances of the City of Sparks, Nevada (Codified through Ordinance No. 2676, adopted July 27, 2026 (Supp. No. 25)) · Sparks Code of Ordinances § 14.05.0500

Corpus is an independent public-information project, not the official City of Sparks website. Stable reference: corpuslaw.us/code/b837167d-ce4e-4f27-83c2-c7b08971ac60

Section 14.05.0500 - Chapter 5—Fire service features.

503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exceptions: 1. The fire code official is authorized to increase the dimension of 150 feet (45 720 mm) where any of the following conditions occur: 1.1. The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. 1.2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided. 1.3. For additions not exceeding 50% of the existing square footage over a five-year period and the fire apparatus access road shall comply with the requirements of this code adoption. 1.4. Additions to existing R-3's shall extend to within 250 feet of all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building subject to the approval of the fire code official. This exception does not include detached structures, ADU's, or similar use. 2. Where approved by the fire code official, fire apparatus access roads shall be permitted to be exempted or modified for solar photovoltaic power generation facilities. 503.3 Marking. Where required by the fire code official, curbs shall be painted red and approved signs or other approved notices or markings that include the words "NO PARKING - FIRE LANE" shall be provided every 100 feet or as required by the fire code official for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designed shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility. 505.1 Address Identification. New and existing buildings shall be provided with approved maintained all-weather address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetic letters. Numbers shall not be spelled out. Each character shall be not less than a nominal height of 6 inches with a minimum ½ inch stroke form residential occupancy and 12 inches with a 1-inch stroke in commercial occupancies, unless otherwise approved by the fire code official. Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole, or other sign or means shall be used to identify the structure. Address identification shall be maintained. SECTION 507 - PROTECTION WATER SUPPLIES 507.3 Fire Flow. Fire flow requirements for buildings or portions of buildings and facilities shall be determined by an approved method. Subject to the approval of the fire authority, if the required fire flow is not available for adequate fire protection, an automatic fire sprinkler system shall be installed throughout the building or buildings. The sprinkler system must meet the requirements of the appropriate NFPA standard. The provisions of this paragraph do not apply if a fire sprinkler system is otherwise required by this chapter or the adopted codes. 507.5.1.1 Hydrant for automatic fire sprinkler and standpipe systems. Buildings equipped with a fire sprinkler system and/or standpipe system installed in accordance with Section 905 shall have a fire hydrant within 100 feet (30 480 mm) of the fire department connections. 507.5.5 Clear space around hydrants. A clear space with a four-foot (4) radius will be maintained around all fire hydrants, except as otherwise required or approved. In addition, where physically possible, a minimum clear space of seven and one-half feet (7 ½') shall be maintained on both sides of a hydrant as measured from the center of the hydrant. Where less than seven and one-half feet (7 ½') of curbing exists, a minimum clear space of four feet (4') on either side of the hydrant is required. In either case, the curb will be painted red to indicate no parking or other obstructions are allowed. See Exhibit #1-A and 1-B below. Exhibit 1-A [image omitted; see the official code] Exhibit 1-B [image omitted; see the official code] Fire hydrant notes: 1. Reinforced Portland cement concrete shall have the following characteristics: 4000 PSI minimum. Compressive strength @ 28 days, minimum, six sacks of cement per cubic yard with a maximum water/cement ratio of 0.45, Air entrainment six percent ± 1.5%, slump at one to four inches. All materials shall conform to SSPWC Section 202. 2. Fire hydrants shall be within six inches of the back edge of the sidewalk when the sidewalk is five feet or less in width. Contact the fire department for proper hydrant location if the sidewalks are wider than five feet. 3. When a landscape strip is between the curb and the sidewalk, or for curbs only, fire hydrants shall be two feet from the face of the curb. 4. Base shall be six inches minimum Type 2, Class B aggregate, compacted to a minimum 95% of maximum dry density. 5. Water pipe shall be ductile iron with field LOK gaskets. 6. Public hydrants shall be factory painted Sherwin Williams Yellow or equivalent. 7. Private hydrants shall be factory painted Sherwin Williams Red or equivalent. 8. All hydrants shall have two 2 ½" hose nozzles and one 5-inch storz nozzle. 9. No fences shall be allowed within four feet of any portion of a fire hydrant. 10. Curb shall be painted red in front of the fire hydrant in accordance with Sparks Municipal Code, Title 14. 11. All fire hydrants shall be tested, inspected, and approved by the Sparks Fire Department prior to combustible material being allowed on site. 508.1 General. Where required by other sections of this code and in all buildings classified as high-rise buildings by the International Building Code as amended in the NRS 477.283 and in all F-1 and S-1 occupancies with a building footprint greater than 500,000 square feet (46 452 m2), a fire command center for fire department operations shall be provided and shall comply with Sections 508.1.1 through 508.1.7. 508.1.6 Required Features. The fire command center shall comply with NFPA 72 and shall contain the following features: 1-18 adopted as written with the addition of: 19. HVAC. The central control station shall be provided with heating, cooling, and ventilation (HVAC) systems that are independent of any other building system or area. HVAC for the central control station shall be connected to the emergency power system. 20. Lighting. Lighting shall provide adequate illumination and shall be on emergency service with additional battery backup emergency lighting. 21. Inside Telephone Line. A telephone connected to the premises telephone exchange shall be provided. A current premises telephone directory shall be placed next to this telephone. 22. Disconnect. The main switch for disconnecting the utility power and any alternate power sources shall be in the fire command center. Switches shall be covered to prevent utility power deeds and any alternate power sources before entering the building. After the switch is operated, no live electrical panels, conductors, or feeds within the premises shall remain energized excluding the emergency electrical circuits. 511.1 Firefighter Equipment Rooms. In all new high-rise buildings of ten (10) or more stories in height, The Fire Department will evaluate the need for firefighter equipment rooms. If required by the Fire Chief, the owner/operator shall provide and equip firefighter equipment rooms intended for the sole use of the fire department during emergency operations. The number, location, type, size, inventory, and access of the firefighter equipment rooms shall be approved by the fire department.

(Ord. 2670, Amended, 04/27/2026;Ord. 2569, § 1, Amended, 11/13/2018)

Ask a question about Sparks law

Corpus searches the Sparks sections it holds and shows the ones that match, with their citations. Free, no sign-in.