1508.05. - Fire hydrant requirements.

(a) General. (1) All fire hydrants shall be approved by the Delaware Public Utility Department and shall conform to the requirements adopted by the American Water Works Association. Hydrants shall have a main valve opening at least five inches in diameter; two, two and one-half (2½) inch hose connections with national standard male threads and a minimum of one, four and one-half (4½) connection with a five inch stortz connection with a locking latch. (2) The location of both public and private fire hydrants shall be approved by the Fire Chief before a building permit is issued. Any deviation from the approved location of any new fire hydrant shall be approved by the Fire Chief or his authorized representative. (3) The minimum size water line to a hydrant shall be six inches. If the line is dead-ended and exceeds 600 feet in length, eight-inch pipe is required. (4) The grade for fire hydrants shall not be less than eighteen inches from the center of the four and one-half outlet. (5) The direction the outlets face shall be approved by the Fire Chief or his authorized representative. (6) Upon completion of a new water main and fire hydrant installations, the Fire Department shall be notified, and the contractor shall demonstrate to the Fire Chief, or authorized representative, that all main valves and fire hydrant valves are open and operable. A fire flow test shall be completed by the contractor on all newly installed fire hydrants prior to acceptance to identify the anticipated fire flow is met and documentation of the pressures and available fire flow submitted to the Fire Department. (7) If it becomes necessary for the contractor to close any main or hydrant valves after they have demonstrated that they are open, the contractor shall notify the Fire Department so that the above procedure may be repeated, insuring that all fire hydrants and mains are placed back in service. (8) All fire hydrants shall be maintained operational, clear of obstructions and properly painted. Fire hydrants shall be painted as follows: Public fire hydrants: Hydrants shall be painted yellow as approved by the Delaware Public Utility Department. Private fire hydrants: The barrel of all private fire hydrants shall be painted bright red. The crown (top) and cap(s) of all private fire hydrants shall be painted white. (9) Each private fire hydrant on water mains that are supplied by fire pumps shall have a permanent sign at the fire hydrant which shall read: "Caution: High Pressure Hydrant Supplied by Fire Pump" The letters shall be bright red and be a minimum of two inches high on a white sign. The sign shall be at the hydrant in a way not to interfere with the operation of, or connection to the hydrant. (10) Prior to the arrival of combustible material on-site or a building beginning vertical construction, fire hydrants that provide fire protection to the building shall be operational and meet the minimum fire flow requirements.

(Ord. 22-55. Passed 6-13-22)

Ask a question about Delaware law

Corpus searches the Delaware sections it holds and shows the ones that match, with their citations. Free, no sign-in.