For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 1508.09 — Fire Department connections

Codified Ordinances of the City of Delaware, Ohio (Codified through Ordinance No. 26-37, enacted September 14, 2026. (Supp. No. 28)) · Delaware Codified Ordinances § 1508.09

Corpus is an independent public-information project, not the official City of Delaware website. Stable reference: corpuslaw.us/code/e925304a-5f22-405a-833d-2ca355b16a3c

1508.09. - Fire Department connections.

(a) An approved Fire Department connection shall be provided to each separate building that has an interior sprinkler, standpipe, or other system that furnishes water for fire suppression purposes. (b) Fire Department connections shall be within 100-feet of a fire hydrant. The distance from the Fire Department connections to fire hydrants shall be the distance as measured by hose laid within a paved surface. (c) Private fire hydrants that service Fire Department connections shall be supplied by the private water main, prior to the point where sprinkler/standpipe lead-ins enter buildings. (d) Fire Department connections shall be located on the same side of the access road as the fire hydrant and be visible and accessible to fire apparatus at all times. (e) Fire Department connections shall be within twenty-five feet of a visible hard surface capable of supporting fire apparatus. (f) Fire Department connections shall be set 24 inches to 42 inches above finished grade. (g) Fire Department connections shall be provided with a 5" stortz connection. Buildings equipped with a NFPA 13D or NFPA 13R system are permitted to be provided with a 2-1/2" connection upon approval by the Fire Chief or representative. (h) All Fire Department connections shall be equipped with a knox box Fire Department connection lock. (i) All Fire Department connections shall be provided with signage indicating: (1) FDC: 5" lettering. (2) Address served: 2" lettering (e.g., 99 S. Liberty St.). (3) Part of the building served: 2" lettering (e.g., full sprinkler coverage, basement only). (4) Type of system served: 2" lettering (e.g., wet sprinkler system, sprinkler, standpipe).

(Ord. 22-55. Passed 6-13-22)

Ask a question about Delaware law

Corpus searches the Delaware sections it holds and shows the ones that match, with their citations. Free, no sign-in.