1508.08. - Fire protection system valves.

(a) All connections from a private fire service main to a building system, shall be provided with a listed indicating valve located to control the water supply and be located on the exterior of the buildings. (b) Large private fire service main systems shall have sectional controlling valves at appropriate points, in order to permit sectionalizing, the system in the event of a break; or for the making of repairs or extensions. The Fire Official shall determine whether a private fire service main system is large enough to require additional valves during the plan review process. (c) All key wrench operated valves within or close to roadway areas shall be provided with a Tyler 6850 screw type valve box or approved equal. (d) Private fire service mains shall be provided the following types of valves: (1) Inside a vault or meter pit: outside screw and yoke (OS&Y) or post indicating valve (PIV) unless approved by the Fire Chief. (2) All other valves: shall be a post indicating valve unless approved by the Fire Chief. (e) All valves connected to a private fire protection system shall be supervised by the fire alarm system unless authorized by the Fire Chief or representative and have a lock installed to prevent tampering.

(Ord. 22-55. Passed 6-13-22)

Ask a question about Delaware law

Corpus searches the Delaware sections it holds and shows the ones that match, with their citations. Free, no sign-in.