§ 1508.07 — Underground fire service mains

Codified Ordinances of the City of Delaware, Ohio (Codified through Ordinance No. 26-37, enacted September 14, 2026. (Supp. No. 28)) · Delaware Codified Ordinances § 1508.07

Corpus is an independent public-information project, not the official City of Delaware website. Stable reference: corpuslaw.us/code/454f3d13-8f2e-44c0-966b-16fe0a735478

1508.07. - Underground fire service mains.

(a) Underground fire service mains shall be designed with the requirements of the Ohio Building Code, the Delaware Fire Prevention Code, National Fire Protection Association (NFPA) Code 24, and [Section] 1508.07. (b) Underground fire service mains shall be installed in accordance with the requirements to National Fire Protection Association (NFPA) Code 24. A copy of the required acceptance test shall be filed with the Fire Department. (c) Fire hydrants shall not be installed on a water main of less than six inches in diameter. Water mains providing fire protection services shall be capable of supplying the needed fire flow for the property being protected as stated in Appendix B of the Delaware Fire Prevention Code. (d) Water mains servicing fire hydrants and fire protection system shall not have meters that reduce the available water flow for fire protection. (e) Fire service water mains servicing two or more fire hydrants shall be a minimum of eight inches in diameter. (f) Fire service water mains, servicing both sprinkler systems or standpipe systems and fire hydrants, shall not be less than eight inches in diameter. (g) Fire service water mains that exceed 600 feet in length and dead-end shall not be less than eight inches in diameter. (h) Underground piping shall be sized to satisfy fire flow requirements and to provide sufficient water supply to fire hydrants, sprinkler systems, standpipe systems, fire pumps, and other systems that furnish water for suppression purposes. (i) Approval of the sizes of piping in fire service main systems by the Fire Department does not relieve the owner, developer, engineer, architect, or contractor, of the responsibility to provide required fire flows and adequate water supply to fire hydrants, sprinkler systems, standpipe systems, fire pumps, or other systems that furnish water for fire suppression purposes, for the building protected. (j) Underground fire service mains that experience two or more failures within a 12-month period or five failures within a 60-month period shall be reviewed for reliability by an engineer including a recommendation to resolve the reliability issue. The property owner shall provide a written plan based on the engineer's recommendation, with a time and include an acknowledgement letter from the responsible party's insurance company on how the problem will be resolved. The written plan shall be adhered to unless the plan is updated including an acknowledgement letter the insurance company. (k) Effective December 31, 2025, underground fire service mains shall serve a single parcel of land or multiple parcels of land owned by the same property owner. If part of the property is sold to a new property owner, a separate private underground fire service main shall be installed to supply the new parcel of land.

(Ord. 22-55. Passed 6-13-22)

Ask a question about Delaware law

Corpus searches the Delaware sections it holds and shows the ones that match, with their citations. Free, no sign-in.