7.13.5 - Overhead Electric Distribution Line Clearance.
A. New Electric Distribution Lines. 1. 13.2kV/7.62kV Grounded Wye. A minimum of 35-foot wide electric distribution clearance is required on real property affected by 13.2kV/7.62kV Grounded Wye electric distribution lines, said clearance shall be a minimum of 17.5 feet from either side of the centerline of the particular distribution pole(s). Clearance criteria in the National Electrical Safety Code may require greater clearance widths in some instances. Additional electric distribution service and clearance requirements are further defined within the Electric Service Standards. B. Existing Electric Distribution Lines. 1. For existing distribution lines and for distribution lines being constructed or reconstructed in developed areas, the utility may elect to perform NESC analysis and calculations to determine that safe and adequate reduced clearance widths can be utilized in lieu of the standard 35 foot width state above. 2. Trees adjacent to overhead electric distribution lines shall comply with Subsection 7.7.7F.7: Trees Adjacent to Overhead Electric Utilities.