7.13.7 - Electric Substation, Interchange, and Switch Station Design.
A. Generally. 1. Standards in this subsection require a basic level of architectural variety, compatible scale, and mitigation of negative impacts. 2. Where the following provisions are silent, the regulations of Subchapter 7: Development Standards, will apply. B. Screening. 1. Generally. a. All screening shall comply with the minimum standards set forth in NERC and NESC. However, to the extent this DDC provides a stricter requirement, this DDC controls. b. Screening is required to obstruct, to the greatest extent possible, internal substation or switch station components from view of the public rights-of-way. This does not require screening of structures, equipment, or buildings that exceed 10 feet in height. 2. Screening Wall. A minimum 10-foot masonry wall is required around the perimeter of the substation, interchange, or switch station to screen the view from public rights-of-way and adjoining properties. 3. Landscaping. a. Trees or any other landscaping shall not be placed within 20 feet of station fences (clearance zone of section G. below). b. Landscaping shall not interfere with the physical security of the site. 4. Gates. a. Gates shall be provided at all entrances. b. Wrought Iron or similar metal gate material shall be permitted. C. Buffering. Buffers are required to minimize potential nuisances such as noise, light, glare, and litter between electric stations and other abutting land uses. Station site expansions are not required to provide space for buffers. Buffering shall not be required when it would compromise station security. Trees shall not be required within clearance zones. 1. Substations or switch stations abutting any property other than an industrial zoning district, shall provide a 20-foot planted strip along the common boundary that includes a combination of five evergreen and deciduous trees and 30 shrubs per 100 linear feet. 2. When located within the clearance zones, low growing shrubs with a maximum mature height of 24 inches shall be used to meet the requirements of this section. 3. Buffering shall not be required when a substation, interchange, or switch station abuts property in an industrial zoning district. 4. Streets and easements shall be considered as buffer. D. Street Tree Standards. 1. Street trees are required in accordance with Subsection 7.7.7, Street Tree Requirements. 2. Street lights may be used in lieu of any required street trees provided they are of the same number and spacing required. E. Tree Canopy Coverage. Tree canopy coverage is required in accordance with Subsection 7.7.4, but shall not be located within the clearance zone as prescribed in Subsection 7.13.7G. In determining the landscape area for the site, only the area located outside the screening wall, clearance zone prescribed in Subsection 7.13.7G, and any transmission easements shall be considered. F. Access and Transportation. Access and transportation into and around the site should be provided to minimize the impacts on adjacent properties, intersections, and the overall street system. Access to the site should be carefully considered to limit the number of entrances that allow greater visibility into the site, while simultaneously allowing for adequate maneuvering of trucks and other heavy equipment necessary to construct, operate, and maintain the site. The following access and transportation standards shall be applicable. 1. Driveways shall be located on the perimeter streets of the lowest classification unless the only reasonable means of providing safe and adequate access to the property, as determined by the City Engineer, is to access a street of higher classification. 2. To the extent possible, driveways shall be located so as not to be directly across from the front yards of residential structures or uses, unless otherwise agreed to by the Director of Development Services or his/her designee. 3. No more than two driveways shall be located on each perimeter street. 4. Driveway separation is subject to the Transportation Criteria Manual. Due to unique access, large vehicular, and trailer turning radius requirements for electric stations, driveway geometry may differ from the Transportation Criteria Manual requirements. 5. Driveways shall be constructed of concrete from the back of edge of the curb to the entrance gate of the site. Gravel is not a permitted driveway material for any driveway outside of the site's perimeter screening wall, unless approved by the City Engineer due to the substation's distance from the roadway. 6. Sidewalks shall be required in accordance with Section 7.8: Access and Circulation, and the Transportation Criteria Manual. Enlarging of substation sites shall not be required to meet the requirements of this section. G. Clearance Zones. 1. A 20-foot clearance zone around the perimeter screening wall free of visual obstructions and climbing aids is required to protect the security and safety of the site. 2. Any landscaping that could be used as a climbing aid shall not be placed within 20 feet of a substation fence. H. Miscellaneous Standards. Development shall comply with this DDC and the NESC and/or NERC standards as applicable and as amended: 1. Height; 2. Noise; 3. Voltage Limitations: 4. Warning Signs; 5. Lighting; 6. Internal Illumination; 7. Vibration; 8. Electric Interference; and 9. Other development standards established by NESC and/or NERC as amended. I. Minor Modifications. Minor modifications on a site plan may be approved by the Director pursuant to Subsection 2.7.2: Minor Modification.
Ask a question about Denton law
Corpus searches the Denton sections it holds and shows the ones that match, with their citations. Free, no sign-in.