Sec. 18-252. - Bearing and anchorage.
Floor joists framing into walls or girders shall be anchored, tied or nailed to secure continuity. The ends of each joist or truss shall have not less than 1½ inches length of bearing on wood or metal nor less than three inches length on hollow of solid masonry units. The ends of beams or girders shall have not less than four inches length of bearing. Beams or joists framing from opposite sides shall lap not less than six inches nor more than 12 inches and be securely bolted or spiked together. When framing end to end, all joists, beams and girders shall be secured together by approved metal ties, straps or scabs. Anchorage of wood joists into masonry walls shall be in accordance with the state building code.
(Code 1973, § 30.29.120)