Sec. 18-260. - Other sheathing.

In lieu of wood board sheathing on exterior walls and roofs of buildings and structures as regulated in this subdivision, materials as shown in tables D and E may be used. TABLE D. WALLS (No edge blocking required) Exterior wall sheathing | Minimum thickness (inches) | Maximum stud spacing on centers (inches) Plywood | 5/16 | 16 Approved fiber board | ½ | 16 Gypsum | ½ | 16 Expanded polystyrene | 1 | 16 TABLE E. ROOFS (No edge blocking required) Roof covering and type of roof | Plywood roof sheathing minimum thickness (inches) | Maximum rafter spacing on centers (inches) Wood and asphalt shingles | ½ | 16 Slate, tile and asbestos cement shingles | ½ | 16 Flat roofs (under 2½: 12 pitch) | ⅝ | 16 Truss roofs (over 2½: pitch) | ½ | 24

(Code 1973, § 30.30.020)