Sec. 49-1542. - Device selection table.
The preferred method of backflow prevention shall be an air gap as defined by section 49-1548. Examples of recommended applications are included in the following table.
This table does not contain all fixtures or devices required to have such protection.
Table 49-1542
Type of Connection | Type of Device to be Used
AG | AVB | PVB | SPVB | DCV | RPBP
Air washers | X
Air compressors (water cooled) | X
Autopsy tables | X
Aspirators, medical | X
Aspirators, weedicide | X
Autoclave and sterilizer | X | X
Boiler feed line | X
Baptismal font | X | X
Bathtub below rim filler | X
Bedpan washer, flushing rim sink | X | X | X
Bidet | X
Brine tank | X
Bottle washer | X
Car wash installation | X
Carbonator | X
Chemical feeder tank | X
Chlorinator | X
Coffee urn | X | X
Cuspidor, dental | X
Chiller tanks | X
Cooking kettle | X
Cooling towers | X
Condensate tank | X
Detergent dispenser | X
Demineralized system | X
Degreasing equipment | X
Dye vats and tanks | X
Developing tanks | X | X | X
Etching tanks | X
Eye wash | X | X | X
Fountain, ornamental | X | X
Garbage can washer | X
Garbage disposers | X | X
Greenhouses | X | X
Hydrotherapy baths | X | X | X
Humidifier tank and boxes | X | X
Hose faucets | X
Hose reels | X | X
Ice maker compressor connection | X
Ice maker water connection | X | X | X
Lab equipment | X
Laundry machine | X | X | X
Pump prime line | X
Photo lab sinks | X | X
Photostat equipment | X
Pipette washer | X
Process heat exchangers | X
Steam cleaner | X
Steam tables | X
Stills | X
Starch tanks | X
Sitz bath | X | X
Sprinkler system (fire) | X | X
Sprinkler system (residential lawn) | X | X
Sprinkler system (commercial lawn) | X
Shampoo basin (beauty shop) | X | X
Serrated faucets | X
Solution tank | X | X
Swimming pool | X | X
Potato peeler | X | X
Ultrasonic baths | X
Vats | X | X
Water closets, tank type | X | X | X
Water closets, flush valve | X | X
Water treatment tanks | X | X
Wash tanks | X | X
Urinal, siphon-jet, blow-out | X | X
Urinal, trough | X | X
AG = Air gap
AVB = Atmospheric vacuum breaker
PVB = Pressure vacuum breaker assembly
SPVB = Spill-resistant pressure vacuum breaker assembly
DCV = Double check valve assembly
RPBP = Reduced pressure backflow preventer assembly
Note 1: All heat exchangers shall be double-wall as required in section 49-1603.