§ 19.28.160 — Groundwater and percolation testing requirements

Municipal Code, City of Rancho Cucamonga, California (Code 2026-09-02) · Rancho Cucamonga Municipal Code § 19.28.160

Corpus is an independent public-information project, not the official City of Rancho Cucamonga website. Stable reference: corpuslaw.us/code/61dd96a4-bca7-4c33-9182-4c86766ae265

§ 19.28.160: Groundwater and percolation testing requirements.

A. Groundwater testing procedures. 1. Test borings in the area of an OWTS shall extend to a minimum of 15 feet unless refusal is reached. Deeper depths may be required depending on site-specific conditions as determined by the City of Rancho Cucamonga building and safety services or the project qualified professional. Site-specific conditions may include, but not be limited to, the proposed depth of the system, local geology, soil types encountered, elevation and terrain, features on site, evidence and/or knowledge of historic ground water levels in the area, and the anticipated fluctuation of the groundwater table in times of normal to above normal annual rainfall. 2. Test borings in the area of a vertical seepage pit or horizontal seepage pit system shall extend to at least 10 feet deeper than the bottom of the proposed pit(s). 3. Since groundwater does not always immediately flow into a test boring, the City of Rancho Cucamonga building and safety services requires a minimum of 72 hours pass before an accurate groundwater measurement is taken. The qualified professional and/or the property owner maintain full responsibility for protecting the public from any hazards related to the test borings. It is recommended that all test borings that encounter groundwater be converted to observation wells so the groundwater conditions can be monitored over time. 4. If the qualified professional does not wish to complete the test borings as observation wells, they can cover the test boring, place safeguards around the borings to prevent unauthorized access and make an appointment for the City of Rancho Cucamonga building and safety services staff to observe the boring at least 72 hours after the boring has been completed. 5. During periods of below normal average rainfall, or after periods of drought where there has not yet been sufficient ground water recharge, the absence of groundwater in test borings in areas where groundwater is suspect may not mean that approval to issue a septic tank permit can be granted. It may be necessary for the City of Rancho Cucamonga building and safety services and the qualified professional to monitor the test borings for a sufficient period of time to determine where groundwater will rise to during normal to above normal rainfall. B. Percolation testing procedure. All percolation testing for dispersal systems except vertical seepage pits in the City of Rancho Cucamonga shall be conducted through the use of the following procedures. The test shall be performed by or under the direct supervision of a California registered professional engineer or geologist. Any deviation shall be authorized only after receiving written approval by the City of Rancho Cucamonga building and safety services. Percolation testing shall be required for all new OWTS for nonresidential development and for residential development comprising more than one dwelling unit, where a percolation report has not previously been completed. A one-lot custom single-family home may use the city's currently adopted California Plumbing Code, Appendix H – Private Sewage Disposal Systems, Section H 3.0 - Area of Disposal Fields and Seepage Pits, and the included Table H 2.1(2) – Design Criteria of Five Typical Soils for the design of the seepage pit or the leech field. 1. Test holes. A minimum of four test holes is required when percolation rates are less than 60 minutes per inch (mpi). A minimum of six test holes is required when the average percolation rate is more than 60 mpi. Additional test holes may be necessary on a site specific basis for reasons that include, but are not limited to, the following: (a) unacceptable or failed tests; (b) areas of the disposal field requiring defined limits for exclusion; (c) the disposal system is located out of a concentrated area; and (d) soil conditions are variable or inconsistent. All test holes shall be representative of the dispersal system installation depth. If the proposed development site has any of the following characteristics, test holes must be extended below the proposed dispersal system installation depth: (i) shallow or consolidated rock or impervious soil layers; (ii) slopes exceeding 25 percent ; or (iii) other factors as might be determined by sound geotechnical engineering practices. 2. There shall be a minimum of 10 feet of soil above any imperious formation such as rock, clay, adobe, and/or water table. Fractured rock and consolidated granites will not be considered as soil. Deep testing may be required to ensure uniform conditions exist below the disposal field. 3. Depending upon the scope of grading for a project, the planning department may require a conceptual grading plan and building and safety services may require a grading plan. If a grading plan is required it should be included with the percolation report submittal. A grading plan helps building and safety services ensure testing was done at the correct depths. Where grading is expected, include the original and finished elevations in the grading plan. For details on how to complete a grading plan contact the building and safety services department. 4. Percolation testing shall be conducted by, and all accompanying reports prepared by a qualified professional. 5. Prior to reviewing a percolation test, building and safety services may require a site evaluation during percolation testing to ensure proper system design, and evaluate site location to ensure that the system will be in compliance. For soil to be considered uniform, test results must fall within 25 percent of the mean percolation rate. Determining the number of percolation tests required will be based on soil conditions and project type. 6. For areas which are primarily sandy loam or sandy clay, a field design of 60 square feet per 100 gallons. 7. For areas which are primarily clay whether considerable sand or gravel, a field design of 90 square feet per 100 gallons. 8. Percolation rates in excess of 120 minutes per inch shall be deemed conclusive evidence that the soil is impermeable and not suitable for an OWTS. C. Percolation testing reports. All testing data and required result information shall be submitted to City of Rancho Cucamonga building and safety services on forms approved by the city. A minimum of three copies is required. All reports shall be signed with an original signature and seal by the consultant who either performed or supervised the testing. All percolation testing is to be performed by a licensed civil engineer or geologist registered in the State of California.

( Ord. No. 911 § 2, 2017 ; Ord. No. 936 § 2, 2018 )

Ask a question about Rancho Cucamonga law

Corpus searches the Rancho Cucamonga sections it holds and shows the ones that match, with their citations. Free, no sign-in.