For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 16.52.5707 — On-demand mobile fueling

Code of Ordinances, City of Sunnyvale, California (includes legislation through Ord. No. 3260-26 adopted August 11, 2026) · Sunnyvale Code of Ordinances § 16.52.5707

Corpus is an independent public-information project, not the official City of Sunnyvale website. Stable reference: corpuslaw.us/code/10b2bcae-75f5-4cab-9dbd-67981e4069a1

§ 16.52.5707: On-demand mobile fueling.

(a) Mobile fueling vehicle. California Fire Code Section 5707.2 is hereby amended to read: 5707.2 Mobile fueling vehicle. An on-demand mobile fueling vehicle shall be one of the following: 1. A tank vehicle complying with NFPA 385 that has chassis-mounted tanks or containers where the aggregate cargo capacity does not exceed 1,200 gallons (4,542 L). 2. A vehicle with one or more chassis-mounted tanks or containers that do not exceed 110 gallons (415 L) individual capacity and having an aggregate capacity that does not exceed 1,200 gallons (4,542 L). 3. A vehicle that carries a maximum of 60 gallons (227 L) of motor fuel in metal safety cans listed in accordance with UL 30 or other approved metal containers each not to exceed 5 gallons (19 L) in capacity. The mobile fueling vehicle shall comply with the requirements of all local, state and federal requirements. Mobile fueling vehicles with a chassis-mounted tank in excess of 110 gallons (415 L) shall comply with the requirements of Section 5706.6, Section 5707, and NFPA 385. The mobile fueling vehicle and its equipment shall be maintained in good repair. Safety cans and approved metal containers shall be secured to the mobile fueling vehicle except when in use. (b) Site plan. California Fire Code Section 5707.3.3 is hereby amended to read: 5707.3.3 Site plan. A site plan shall be developed for each location at which mobile fueling occurs. The site plan shall be in sufficient detail to indicate: all buildings, structures, lot lines, property lines, and appurtenances on site and their use or function; all uses adjacent to the lot lines of the site; fueling locations, the locations of all storm drain openings and adjacent waterways or wetlands; information regarding slope, natural drainage, curbing, impounding and how a spill will be retained upon the site property; and the scale of the site plan. (c) Equipment. California Fire Code Section 5707.5 is hereby amended to read: 5707.5 Equipment. Mobile fueling equipment shall comply with Sections 5707.5.1 through 5707.5.5. (d) Break-away device. California Fire Code Section 5707.5 is hereby amended by adding 5707.5.5 to read: 5707.5.2 Break-away device. A listed break-away device shall be provided at the nozzle. Exception: Mobile fueling vehicles equipped with an approved brake interlock tied to the nozzle holder that prohibits movement of the mobile fueling vehicle when the nozzle is removed from its holder. (e) Operations. California Fire Code Section 5707.6.7 is hereby amended to read: 5707.6.7 Bonding. A means for bonding the mobile fueling vehicle to the motor vehicle shall be provided. Such bonding means shall be employed during fueling operations.

( Ord. 3101-16 § 1 ; Ord. 3148-19 § 1 ; Ord. 3201-22 § 1 )

Ask a question about Sunnyvale law

Corpus searches the Sunnyvale sections it holds and shows the ones that match, with their citations. Free, no sign-in.