§ 16.52.9000 — Firefighter air replenishment systems
Code of Ordinances, City of Sunnyvale, California (includes legislation through Ord. No. 3260-26 adopted August 11, 2026) · Sunnyvale Code of Ordinances § 16.52.9000
Corpus is an independent public-information project, not the official City of Sunnyvale website. Stable reference: corpuslaw.us/code/7ebc9e37-b1b7-4098-a8f1-a8dca2fc69bf
§ 16.52.9000: Firefighter air replenishment systems.
(a) Breathing air supply. Appendix L Section L104.5 of the 2024 International Fire Code is hereby amended to read: L104.5 Breathing air supply. A stored air pressure system in accordance with Section L104.5.1 shall be provided. In addition, the FARS shall be supplied by an external mobile air connection in accordance with Section L104.14. There shall be a means provided to bypass the stored pressure air supply located at the external mobile air connection. (b) Fill station location. Appendix L Section L104.13.1 of the 2024 International Fire Code is hereby amended to read: L104.13.1 Location. Fill stations for refilling breathing air cylinders shall be located as follows: 1. Fill stations shall be provided at the third floor above and below the ground level floor and every third floor level thereafter. 2. On floor levels requiring fill stations, one fill station shall be provided adjacent to a required exit stair at a location designation by the fire code official. In buildings required to have three or more exit stairs, additional fill stations shall be provided at a ratio of one fill station for every three stairways. (c) External mobile air connection location. Appendix L Section L104.14.1 of the 2024 International Fire Code is hereby amended to read: L104.14.1 Location. The location of the external mobile air connection shall be accessible to mobile air apparatus and approved by the fire code official. (d) Emergency fill station. Appendix L Section L104 of the 2024 International Fire Code is hereby amended by adding Section L104.16 to read: L104.16 Emergency fill panel (EFP). In addition to the fill stations required in Section L104.13, an emergency rapid fill panel shall be provided at an approved location in the stair enclosure at the third floor above and below the ground level floor and every two floor levels thereafter.
( Ord. 3101-16 § 1 ; Ord. 3148-19 § 1 ; Ord. 3201-22 § 1 ; Ord. 3247-25 , 10/21/2025 )
Ask a question about Sunnyvale law
Corpus searches the Sunnyvale sections it holds and shows the ones that match, with their citations. Free, no sign-in.