§ 81.2.9: Power source for smoke-control systems. [Geological/Climatic]

Section 909.11.3 of the California Building Code, 2025 Edition, is hereby added to read in its entirety as follows: 909.11.3 Primary and Standby Power Source. The smoke-control system shall be supplied with two sources of power. Primary power shall be from the normal building power systems. Secondary power shall be from an approved standby source complying Chapter 27 of this code. The standby power source and its transfer switches shall be in a room separate from the normal power transformers and switch-gear and ventilated directly to and from the exterior. The room shall be enclosed with not less than 1-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. Transfer to full standby power shall be automatic and within 60 seconds of failure of the primary power. The systems shall comply with the Electrical Code. Exception: The secondary power is not required for pressurized enclosures in buildings of less than 5 floors used for human occupancy.