§ 81.2.21: Structural observations for seismic resistance. [Geological]
Section 1704.6.1 of the 2025 Edition of the California Building Code is amended to read as follows: 1704.6.1 Structural observations for structures. Structural observations shall be provided for those structures where one or more of the following conditions exist: 1. | The structure is classified as Risk Category III or IV. 2. | The structure is a high-rise building. 3. | A lateral design is required for the structure or portion thereof. Exception: One-story wood framed Group R-3 and Group U Occupancies less than 2,000 square feet in area, provided the adjacent grade is not steeper than 1 unit vertical in 10 units horizontal (10% sloped), assigned to Seismic Design Category D. 4. | Such observation is required by the registered design professional responsible for the structural design. 5. | Such observation is specifically required by the building official.