§ 18-29-606.5.9 — Pressure relief valve requirements
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-606.5.9
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/0a3e2988-1b7f-405e-88da-31ea7f48a223
18-29-606.5.9 Pressure relief valve requirements.
Each pressure relief valve shall be a minimum of 3/4 inch (20 mm) and shall be equipped with a test lever. In addition, an automatic vacuum relief valve shall be installed on such tanks with a 24-mesh screen of bronze or stainless steel. The area of the screening shall be 50 percent greater than the opening it serves. All equipment of a hydropneumatic system shall be capable to withstand the designed working pressure. Exception: This section shall not apply to pressurized captive air diaphragm/bladder tanks.