§ 18-29-607.2.1.2 — Demand recirculation controls for distribution systems
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-607.2.1.2
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/bb84fe65-7fdb-44d6-9d0c-2f59d6a43292
18-29-607.2.1.2 Demand recirculation controls for distribution systems.
A water distribution system having one or more recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe shall be a demand recirculation water system. Pumps shall have controls that comply with both of the following: 1. The control shall start the pump upon receiving a signal from the action of a user of a fixture or appliance, sensing the presence of a user of a fixture, or sensing the flow of hot or tempered water to a fixture fitting or appliance. 2. The control shall limit the temperature of the water entering the cold water piping to 104°F (40°C). (Added Coun. J. 10-14-21, p. 37722, Art. VI, § 27)