§ 18-29-606.6 — Test of distribution pipes
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-606.6
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/ca2e2b7c-0981-4691-af2f-d7dfa9e51bc2
18-29-606.6 Test of distribution pipes.
The entire water distribution system within buildings shall be tested utilizing a water or air pressure test. All piping, fittings, valves and equipment except any atmospheric tank shall be tested to 1 1/2 times its designed pressure but not less than 100 psi (690 kPa). When the test pressure exceeds 100 psi (690 kPa) only a hydrostatic test shall be given. (Amend Coun. J. 10-14-21, p. 37722, Art. VI, § 26)
Ask a question about Chicago law
Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.
