§ 8-1-4-301.4 — Amendment to Section 301.4 of the UMC
Salina Code, City of Salina, Kansas (Codified through Ordinance No. 26-11299 adopted August 24, 2026. (Supp. No. 19)) · Salina Municipal Code § 8-1-4-301.4
Corpus is an independent public-information project, not the official City of Salina website. Stable reference: corpuslaw.us/code/29c403b5-4d04-46a7-86db-4685899882f5
Sec. 8-1-4-301.4. - Amendment to Section 301.4 of the UMC.
Section 301.4 of the UMC is amended to read as follows: Sec. 301.4 Electrical Connections. For equipment regulated by this code: (1) Equipment requiring electrical connections of more than 50 volts shall have a positive means of disconnect adjacent to and in sight from the equipment served. Exception: Other power disconnect means shall be acceptable when in accordance with NFPT 70. (2) A 120 volt receptacle shall be located within 25 feet (7620 mm) of the equipment for service and maintenance purposes. The receptable outlet shall be on the supply side of the disconnect switch. The receptacle need not be located on the same level as the equipment. Exception: The receptacle is not required for replacement of existing equipment in the same location when the existing equipment conformed with adopted code standards at the time of installation. (3) Electrical wiring, controls, and connections to equipment and appliances regulated by this code shall be in accordance with NFPA 70.
(Ord. No. 25-11269, § 1, 12-8-25)