Sec. 8-1-4-304.1. - Amendment to Section 304.1 of the UMC.
Section 304.1 of the UMC is amended to read as follows: Sec. 304.1 General Appliances shall be located with respect to building construction and other equipment so as to permit access to the appliance. Sufficient clearance shall be maintained to permit cleaning of heating surfaces; the replacement of filters, blowers, motors, burners, controls, and vent connections; the lubrication of moving parts where necessary; the adjustment and cleaning of burners and pilots; and the proper functioning of explosion vents, where provided. For attic installation, the passageway and servicing area adjacent to the appliance shall be floored. [NFPA 54:9.2.1] Unless otherwise specified, not less than 30 inches (762 mm) in depth, width, and height of working space shall be provided. Exception: 1. A platform shall not be required for unit heaters or room heaters. 2. For replacement central furnaces and boilers the unobstructed depth need only be 24".
(Ord. No. 25-11269, § 1, 12-8-25)