For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 8-1-4-310.1.1 — Amendment to Section 310.1.1 of the UMC

Salina Code, City of Salina, Kansas (Codified through Ordinance No. 26-11299 adopted August 24, 2026. (Supp. No. 19)) · Salina Municipal Code § 8-1-4-310.1.1

Corpus is an independent public-information project, not the official City of Salina website. Stable reference: corpuslaw.us/code/bb791771-6e59-4cef-b19b-fd8d832c5d49

Sec. 8-1-4-310.1.1. - Amendment to Section 310.1.1 of the UMC.

Section 310.1.1 of the UMC is amended to read as follows: Sec. 310.1.1 Condensate Pumps. Where approved by the Authority Having Jurisdiction, condensate pumps shall be installed in accordance with the manufacturer's installation instructions. Pump discharge shall rise vertically to a point where it is possible to connect to a gravity condensate drain and discharged to an approved disposal point. Each condensing unit shall be provided with a separate sump and interlocked with the equipment to prevent the equipment from operating during a failure. Separate pumps shall be permitted to connect to a single gravity indirect waste where equipped with check valves and approved by the Authority Having Jurisdiction. Exception: Any air handling unit containing a condensing unit and a heating element shall be considered one unit.

(Ord. No. 25-11269, § 1, 12-8-25)

Ask a question about Salina law

Corpus searches the Salina sections it holds and shows the ones that match, with their citations. Free, no sign-in.