Sec. 8-1-4-310.0. - Amendment to Section 310.0 of the UMC.

Section 310.0 of the UMC is amended to read as follows: Sec. 310.0 Electrical Connections. Equipment regulated by this code requiring electrical connections of more than 50 Volts shall have a positive means of disconnect adjacent to and in sight from the equipment served. A 120 volt receptacle shall be located within 25 feet (7620 mm) of the equipment for service and maintenance purposes. The receptacle is not required for replacement of existing equipment in the same location. The receptacle must be located on the same level as the equipment and be accessible. Low voltage wiring of 50 Volts or less within a structure shall be installed in a manner to prevent physical damage.

(Ord. No. 25-11269, § 1, 12-8-25)