§ 7-214 — International Building Code amended; Section 903.2.4. Group F-1
Code of Ordinances of the City of Lee's Summit, Missouri (Codified through Ordinance No. 10423, enacted July 14, 2026 (Supp. No. 56)) · Lee's Summit Code of Ordinances § 7-214
Corpus is an independent public-information project, not the official City of Lee's Summit website. Stable reference: corpuslaw.us/code/0b1cc54a-2dc8-49b6-8b1c-68fa8ba817d1
Sec. 7-214. - International Building Code amended; Section 903.2.4. Group F-1.
Section 903.2.4 Group F-1 is hereby amended to read as follows: Group F-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following conditions exists: 1. A Group F-1 fire area exceeds 12,000 square feet (1115 m 2 ). 2. A Group F-1 fire area is located more than two stories above grade plane. 3. The combined area of all Group F-1 fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2230 m 2 ). 4. A Group F-1 occupancy is used to manufacture lithium-ion or lithium metal batteries. 5. A Group F-1 occupancy is used to manufacture vehicles, energy storage systems or equipment containing lithium-ion or lithium metal batteries where the batteries are installed as part of the manufacturing process.
(Ord. No. 10422, § 1, 7-14-2026)