§ 7-222 — International Building Code amended; Section 905.3.1. Height
Code of Ordinances of the City of Lee's Summit, Missouri (Codified through Ordinance No. 10423, enacted July 14, 2026 (Supp. No. 56)) · Lee's Summit Code of Ordinances § 7-222
Corpus is an independent public-information project, not the official City of Lee's Summit website. Stable reference: corpuslaw.us/code/fb36c317-57c9-4178-9a4b-c8e7482cc8bd
Sec. 7-222. - International Building Code amended; Section 905.3.1. Height.
Section 905.3.1 Height is hereby amended to read as follows: Class III standpipe systems shall be installed throughout buildings where any of the following conditions exist: 1. Three or more stories are above or below grade plane. 2. The floor level of the highest story is located more than 30 feet (9144 mm) above the lowest level of the fire department vehicle access. 3. The floor level of the lowest story is located more than 30 feet (9144 mm) below the highest level of fire department vehicle access. EXCEPTIONS: 1. Class I standpipes are allowed in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. 2. Class I standpipes are allowed in Group B and E occupancies. 3. Class I standpipes are allowed in parking garages. 4. Class I standpipes are allowed in basements equipped throughout with an automatic sprinkler system. 5. Class I standpipes are allowed in buildings where occupant-use hose lines will not be utilized by trained personnel or the fire department. 6. In determining the lowest level of fire department vehicle access, it shall not be required to consider either of the following: 6.1. Recessed loading docks for four vehicles or less. 6.2. Conditions where topography makes access from the fire department vehicle to the building impractical or impossible.
(Ord. No. 10422, § 1, 7-14-2026)
Ask a question about Lee's Summit law
Corpus searches the Lee's Summit sections it holds and shows the ones that match, with their citations. Free, no sign-in.