§ 7-215 — International Building Code amended; Section 903.2.7. Group M

Code of Ordinances of the City of Lee's Summit, Missouri (Codified through Ordinance No. 10423, enacted July 14, 2026 (Supp. No. 56)) · Lee's Summit Code of Ordinances § 7-215

Corpus is an independent public-information project, not the official City of Lee's Summit website. Stable reference: corpuslaw.us/code/9f52a092-5450-4ce5-b6b3-d4873659c02c

Sec. 7-215. - International Building Code amended; Section 903.2.7. Group M.

Section 903.2.7 Group M is hereby amended as follows: Group M. An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy where one of the following conditions exist: 1. A Group M fire area exceeds twelve thousand (12,000) square feet (1,115 m 2 ). 2. A Group M fire area is located more than two (2) stories above grade plane. 3. The combined area of all Group M fire areas on all floors, including any mezzanines, exceeds twenty-four thousand (24,000) square feet (2,230 m 2 ).

(Ord. No. 10422, § 1, 7-14-2026)