§ 7-216 — International Building Code amended; Section 903.2.9. Group S-1

Code of Ordinances of the City of Lee's Summit, Missouri (Codified through Ordinance No. 10423, enacted July 14, 2026 (Supp. No. 56)) · Lee's Summit Code of Ordinances § 7-216

Corpus is an independent public-information project, not the official City of Lee's Summit website. Stable reference: corpuslaw.us/code/0cba66d9-fb48-437c-bf7b-3855880b970a

Sec. 7-216. - International Building Code amended; Section 903.2.9. Group S-1.

Section 903.2.9 Group S-1 is hereby amended to read as follows: Group S-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists: 1. A Group S-1 fire area exceeds 12,000 square feet (1115 m 2 ). 2. A Group S-1 fire area is located more than two stories above grade plane. 3. The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2230 m 2 ). 4. A Group S-1 fire area used for the storage of commercial motor vehicles where the fire area exceeds 5,000 square feet (464 m 2 ). 5. A Group S-1 fire area used for the storage of lithium-ion or lithium metal powered vehicles where the fire area exceeds 500 square feet (46.4 m 2 ).

(Ord. No. 10422, § 1, 7-14-2026)