Sec. 7-217. - International Building Code amended; Section 903.2.9.1. Repair garages.
Section 903.2.9.1 Repair garages is hereby amended to read as follows: An automatic sprinkler system shall be provided throughout all buildings used as repair garages in accordance with Section 406, as shown: 1. Buildings two (2) or more stories in height, including basements, with a fire area containing a repair garage exceeding five thousand (5,000) square feet (464 m 2 ). 2. Buildings no more than one story above grade plane with a fire area containing a repair garage exceeding five thousand (5,000) square feet (464 m 2 ). 3. Buildings with repair garages servicing vehicles parked in basements. 4. A Group S-1 fire area used for the repair of commercial trucks or buses where the fire area exceeds five thousand (5,000) square feet (464 m 2 ).
(Ord. No. 10422, § 1, 7-14-2026)