Sec. 7-221. - International Building Code Section amended; Section 903.4.3.1. Notification devices.

Section 903.4.3.1 Notification devices is hereby added to read as follows: Where an automatic fire sprinkler system is installed in a new or existing building, audible and visible notification appliances shall be installed throughout the building as follows: 1. Audible notification appliances shall be installed to be audible at 15 dBa above sound pressure level throughout the building. 2. Visible notification appliances shall be installed in all public and common use areas, restrooms and corridors and in accordance with NFPA 72. EXCEPTION: The requirements of this section do not apply to Group R-3 occupancies.

(Ord. No. 10422, § 1, 7-14-2026)