§ 403 — WATER SUPPLY SYSTEM

Comprehensive Development Regulations for the City of Flowood; partial · Flowood Development Regulations § 403

Corpus is an independent public-information project, not the official City of Flowood website. Stable reference: corpuslaw.us/code/c1df72c7-20f8-4529-9ed2-04dc642fc94f

SECTION 403 WATER SUPPLY SYSTEM

403.1 Water mains properly connected with the City of Flowood's water supply system shall be provided through a system of appropriate piping and valves and shall be designed and constructed in such a manner to adequately serve all lots shown on the subdivision plat for both domestic and fire protection purposes and will adhere to the minimum requirements set forth hereinbelow:

a. Water distribution systems shall be designed using the Hardy-Cross Analysis. The Hazen-Williams formula shall be used in computing head loss.

b. Water distribution systems shall be designed for the peak hour flow or the maximum day flow plus fire flow whichever is greater.

c. The water distribution system shall be designed such that the following range of dynamic pressures are provided: fifty psi to eighty psi (50-80 psi) for average daily flows; twenty psi to forty psi (20-40 psi) for peak hour flows; twenty psi to thirty psi (20-30 psi) for maximum day flow plus fire flow. The minimum dynamic pressure at any point shall be twenty (20) psi.

d. The maximum design velocity in distribution mains shall not exceed five (5) fps.

e. Water distribution mains shall be laid out on a grid system with cross-connections at cross-streets. Dead-end pipes shall be avoided whenever possible.

f. Valves shall be installed at each intersection or change in pipe size and shall be placed such that no single case of pipe breakage shall require shut-off from service of an artery of more than five-hundred feet (500’) of pipe in high value districts, more than eight-

hundred feet (800’) of pipe in any area, or more than twelve lots in a subdivision.

g. The distribution and spacing of hydrants shall ultimately be determined by the City fire department on a project-by-project basis. At a minimum, the spacing of fire hydrants in the residential areas shall be such that no lot will be in excess of 400 feet from a fire hydrant with the measurement being made along the streets. In commercial districts, fire hydrants shall be spaced a minimum of 300’. All fire hydrants shall include a separate valve.

h. Main pipe size for water mains shall be a minimum of six inches where the line length is 600’ or less and is tied to or loops back into a larger diameter line or a minimum of eight inches beyond those conditions.

i. For Site Plan Projects, the minimum pipe size shall be as determined by the Owner’s design team.

j. Water lines shall be gridded or looped with more than one source of supply for properties that are to be subdivided unless otherwise approved by the City.

k. Service lines for residential houses shall be a minimum of 1”. Water service line locations shall be marked with a “W” on the curb face. Services lines shall be CTS high density polyethylene tubing (CTS) pipe SDR 9 for use in potable water applications.

l. All commercial service lines and residential sprinkler lines must be equipped with an appropriate backflow preventer as approved by the Mississippi State Department of Health.

m. A 12-gauge copper clad steel tracer wire shall be installed along all water mains and service lines. The tracer wire shall have HDPE insulation intended for direct bury, color coated per APWA standards for the water utility and have connectors rated for direct bury. All tracer wire shall be installed as a complete system, complete with connectors, magnesium anode ground rods, and terminal stations at each fire hydrant, water valve, and termination locations. All tracer wire installations shall undergo a location test by the city prior to acceptance. Any areas not able to be located using typical low frequency line tracing equipment shall be repaired by the Subdivider. Tracer wire shall be equal to Copperhead 1230-HS or approved equal and all accessories shall be Copperhead Industries or approved equal.

n. The water main pipe shall be PVC as described below unless otherwise directed by the City.

403.2 PVC Water Main Pipe

a. All PVC pipe and fittings four (4) inches to twelve (12) inches in diameter shall conform to the latest edition of AWWA C-900 and shall be made from Class 12454-A or B materials per the latest edition of ASTM D-1784. Pipe shall be a minimum of SDR 18 unless otherwise specified, for a minimum working pressure rating of 235 PSI. All pipes shall conform to the outside diameter (OD) dimensions of ductile iron pipe to facilitate

use of DIP fittings, standard cast iron valves and specials. All joints shall be elastomeric sealed conforming to the latest edition of ASTM F-477. Gasketed joint assembly shall meet the requirements of ASTM D 3139. All pipe that is noted to have nitrile gasket shall be clearly marked to ensure pipe can be easily identified for installation in the proper location.

b. All PVC pipe (3) inches and smaller in diameter shall conform to the latest edition of ASTM D-2241 and shall be made from Type 1120 material. Pipe shall be a minimum of SDR 26 unless otherwise specified, for a working pressure of 150 PSI. All joints shall be solvent welded in accordance with the latest edition of ASTM D-2855 with the solvent cement conforming to the latest edition of ASTM D-2564.

c. Pipes 12” in diameter or greater shall be of material as required by the City.

d. All jointing shall be made in accordance with the manufacturer’s recommendations.

e. Al pipes shall bear the National Sanitation Foundation (NSF) seal of approval.

f. Fittings for PVC pipe water mains 6” and larger shall be ductile iron as per the following section.

403.3 Ductile Cast Iron Pipe & Fittings

a. Ductile iron pipe shall be water pipe manufactured in accordance with AWWA C 151 (ANSI A21.51).

b. Fittings can be either AWWA C110 (full size fittings) or AWWA C153 (compact fittings).

c. All fittings shall be ductile iron and shall conform to the latest edition of AWWA specifications for ductile iron fittings.

d. All ductile iron pipe and fittings shall be factory-coated on the outside with coal tar enamel conforming to the latest edition of AWWA C105 (ANSI A21.5) and lined inside with a minimum of 1/16 inch cement-mortar lining in accordance with the latest edition of AWWA C104 (ANSI A21.4).

e. All pipe and fittings shall be tested for minimum 150 PSI water working pressure, laying conditions Type 2, flat bottom trench without blocking, tamped, backfilled and under five (5) feet of cover.

f. All pipe and fittings shall be encased with an 8-mil thick loose polyethylene encasement in accordance with the latest edition of AWWA C-105 (ANSI A21.5).

g. Joints for ductile cast iron pipe shall be slip-on type unless otherwise specified. Slip-on joint shall conform to the latest edition of AWWA C 111 (ANSI A21.11) except that the joints shall be made with a special gasket seal Super-Bel Tite as manufactured by the Clow Corporation or approved equal. Lubricants shall be non-toxic, odorless,

tasteless and shall not support bacteria and shall be specifically manufactured for the pipe utilized.

h. Mechanical joint pipes shall conform to the latest edition of AWWA C 111 (ANSI A21.11).

i. All joints for fittings, valves and specials shall be mechanical joints unless otherwise specified. Meg-a-lug or approved equal required on all fittings.

j. If flexible joint or river crossing pipe is required and/or indicated in the project plans or specifications the joint shall be designed for a maximum deflection of 15 degrees, and a maximum working pressure rating of 250 psi. The type shall be the USIFLEX joint as manufactured by U.S. Pipe or an approved equal.

k. All fittings shall be cast from ductile iron in accordance with ANSI/AWWA C153/A21.53. Fittings shall be listed by an approved certifying agency as conforming to the requirements of ANSI/NSF 61. The working pressure rating shall be 350 psi.

403.4 The minimum requirements set forth apply to single family residential detached developments and small-scale commercial developments (scale as determined by the City) and may be increased for higher density residential or commercial developments should conditions warrant.

403.5 All elements of any distribution system connected to the municipal water distribution system shall be installed in accordance with the recommendations of and approval of the Mississippi State Department of Health. The physical connection between the system installed by the subdivider and the municipal system shall not be made until the system being installed has been sterilized and a clearance report has been obtained from the Mississippi State Department of Health.

403.6 The City shall be notified twenty-four (24) hours in advance prior to the connection of any water main to the City of Flowood's system. The City of Flowood shall make all physical connections and shall be reimbursed by the developer per the City of Flowood Fee Schedule unless otherwise directed by the City.

403.7 Water Line Testing: The following tests shall be required on all new water lines installed that are intended to be maintained by the City.

a. Hydrostatic Test:

1. A hydrostatic test(s) shall be performed on the newly laid water system by the Contractor with a hydrostatic pressure of one-hundred fifty (150) psi. This test shall last for a minimum of four (4) hours unless a variance for unusual conditions is approved by the City Engineer.

2. The test shall be performed so that all 4 hours of the test are during normal work hours for the City of Flowood.

3. The line shall be slowly filled with water and all air expelled from the line prior to performing pressure test.

4. Test pressure shall not vary by more than plus/minus 5psi during the duration of the test.

5. All exposed items such as pipes, fittings, valves, hydrants, etc. shall be carefully examined by the Contractor during the test. Any cracked or defective items shall be removed and replaced by the Contractor and then the test shall be repeated.

b. Leakage Test:

1. A leakage test shall be conducted by the Contractor along with the pressure test. The duration of each leakage test shall be 4 hours. During the test, the main shall be subjected to a pressure of 150 psi unless shown to be different in piping schedule. This test can be performed at the same time as the pressure test.

2. Leakage shall be defined as the quantity of water that must be supplied into the newly laid pipe or any valved section thereto to maintain the specified leakage test pressure after the air in the pipe has been expelled and the pipe is filled with water.

3. No pipe installation will be accepted if the leakage is greater than that determined by the formula “L=(SD(P^0.5))/148,000”. Where “L” is the allowable leakage in gallons per hour, “S” is the length of pipe tested in feet, and “D” is the nominal diameter of the pipe measured in inches and P is the average test pressure during the hydrostatic test, in pounds per square inch.

c. If, in the opinion of the City Engineer, additional testing is required, such additional testing shall be performed by the developer at his own expense. All water mains, hydrants, valves, service laterals and appurtenances shall be constructed in accordance with the approved construction plans and any standard drawings and specifications adopted by the City of Flowood, Mississippi.