24.12.405 Section 908.3 Added; Horizontal Wet Venting for other than bathroom groups.

Section 908.3 is added to the Uniform Plumbing Code to read as follows: Section 908.3. The wet vent shall be sized based on the fixture unit discharge, using only 1 and 2 dfu fixtures, into the wet vent. The wet vent shall be not less than 2 inches (50 mm) in diameter for 4 drainage fixture units (dfu) or less, and not less than 3 inches (80 mm) in diameter for 5 dfu or more. The dry vent shall be sized in accordance with Table 702.1 and Table 703.2 based on the total fixture units discharging into the wet vent. Kitchen sinks, sinks with disposers and sinks with dishwashers shall not be used in a horizontal wet venting system. ().

(Ord. 21817 §41; December 15, 2025)