24.12.385 Section 904.1 Amended; Size.
Section 904.1 of the Uniform Plumbing Code is amended to read as follows: 904.1 Size. The size of vent piping shall be determined from its length and the total number of fixture units connected thereto, as set forth in Table 703.2. The diameter of an individual vent shall not be less than one and one-fourth (1-1/4) inches nor less than one-half (1/2) the diameter of the drain to which it is connected. In addition, the drainage piping of each building and each connection to a public sewer or a private sewage disposal system shall be vented by means of one or more vent pipes, the aggregate cross-sectional area of which shall not be less than that of the largest required building sewer, as determined from Table 703.2. EXCEPTION: Minimum Size of Stack Vent or Vent Stack. Any structure in which a building drain is installed shall have at least one stack vent or vent stack not less than three (3) inches in diameter. (: Ord. 20525 §76, August 21, 2017).
(Ord. 21817 §39; December 15, 2025)