24.12.365 Section 810.2 Amended; Sumps, Condensers, and Intercepting Tanks.

Section 810.2 of the Uniform Plumbing Code is amended to read as follows: 810.2 Sumps, Condensers, and Intercepting Tanks. Sumps, condensers, or intercepting tanks which are constructed of concrete shall have walls and bottom not less than four (4) inches in thickness, and the inside shall be cement plastered not less than one-half (1/2) inch in thickness. Condensers constructed of metal shall be not less than No. 12 U.S. Standard gauge (0.109 inch) and all such metal condensers shall be protected from external corrosion by an approved bituminous coating. EXCEPTION: Type 3 or greater RCP shall be approved.

(Ord. 20525 §72, August 21, 2017)