25.06.832 IRC Section 1601.1.2 Amended; Underground Duct Systems.
Section 1601.1.2 of the International Residential Code is amended to read as follows: Underground duct systems shall be constructed of approved concrete, clay, metal or plastic. The maximum design temperature for systems utilizing plastic duct and fittings shall be 150 degrees F. Metal ducts shall be protected from corrosion in an approved manner or shall be completely encased in concrete not less than 2 inches thick. Nonmetallic ducts shall be installed in accordance with the manufacturer’s instructions. Plastic pipe and fitting materials shall conform to cell classification 12454-B of ASTM D1248 or ASTM S1784 and external loading properties of ASTM D2412. Ducts shall slope to a drainage point that has access. Ducts shall be sealed and secured prior to encasing the ducts in concrete or direct burial. Metallic ducts having an approved protective coating and nonmetallic ducts shall be installed in accordance with the manufacturer’s instructions. ().
(Ord. 21113 §60; August 23, 2021)