§ 15.24.700 — NFPA 13, 2025 Edition
Murrieta Municipal Code (2026 S-23 through Ord. 639-26) · Murrieta Municipal Code § 15.24.700
Corpus is an independent public-information project, not the official City of Murrieta website. Stable reference: corpuslaw.us/code/d5035312-8644-4cae-b4d1-48aceb8bedec
15.24.700 NFPA 13, 2025 Edition.
NFPA 13, 2025 Edition, Standard for the Installation of Sprinkler Systems is hereby amended as follows: Section 16.12.3.3 is hereby revised as follows: 16.12.3.3 Fire department connections (FDC) shall be of an approved type. The FDC shall contain a minimum of two 2½” inlets. The location shall be approved and be no more than 40 feet from a public or private hydrant. The size of the piping and the number of inlets shall be approved by the fire code official. Fire department inlet connections shall be painted OSHA safety red. When the fire sprinkler density design requires 500 gpm (including inside hose stream demand) or greater, or a standpipe system is included, four 2½” inlets shall be provided. (Ord. 626-25 § 1 (part), 2025)