§ 15.24.760 — Amended - Table B105.1(2)

Murrieta Municipal Code (2026 S-23 through Ord. 639-26) · Murrieta Municipal Code § 15.24.760

Corpus is an independent public-information project, not the official City of Murrieta website. Stable reference: corpuslaw.us/code/eb32fa9c-89c3-4e99-acc8-51b041fbe378

15.24.760 Amended - Table B105.1(2).

TABLE B105.2 REQUIRED FIRE-FLOW FOR BUILDINGS OTHER THAN ONE AND TWO FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES AUTOMATIC SPRINKLER SYSTEM (Design Standard) | MINIMUM FIRE-FLOW (gallons per minute) | FLOW DURATION (hours) No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) Section 903.3.1.1 (NFPA 13) or Section 903.3.1.2 (NFPA13R) of the California Fire Code | 50% of the value in Table B105.1(2) not less than 2,500 for multi-family, not less than 3,000 for commercial not less than 3,500 for industrial | Duration for multi-family, 2 hoursDuration for commercial, 3 hoursDuration for industrial, 4 hours For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m *Or as otherwise required by the Fire Code official (Ord. 626-25 § 1 (part), 2025)