§ 15.24.750 — Amended - Table B105.1(1)

Murrieta Municipal Code (2026 S-23 through Ord. 639-26) · Murrieta Municipal Code § 15.24.750

Corpus is an independent public-information project, not the official City of Murrieta website. Stable reference: corpuslaw.us/code/0b19c59f-1afe-4383-b424-caaf89ca4d48

15.24.750 Amended - Table B105.1(1).

TABLE B105.1(1) REQUIRED FIRE-FLOW FOR ONE AND TWO FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES CALCULATION AREA (square feet) | AUTOMATIC SPRINKLER SYSTEM (Design Standard) | MINIMUM FIRE-FLOW (gallons per minute) | FLOW DURATION (hours) 0-3,600 | No automatic sprinkler | 1,500 | 2 3,601 and greater | No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) at the required fire-flow rate, but not less than 2 hours. 0-3,600 | Section 903.3.1.3 of the California Fire Code or Section 313.3 of the California Residential Code | 500 | 1/2 3,601 and greater | Section 903.3.1.3 of the California Fire Code or Section 313.3 of the California Residential Code | ½ value in Table B105.1(2) but not less than 875 | 1 For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m (Ord. 626-25 § 1 (part), 2025)