15.24.770 Section B105.4 Added - Projects Located in Fire Severity Zones.

All new buildings constructed or installed that are located within a High and Very High Fire Hazard Severity Zone, as designated by the Director of Forestry and Fire Protection or as subsequently amended, the minimum fire-flow requirements shall be increased by 500 gallons per minute (GPM) at a residual pressure of 20 psi for a minimum duration of 2 hours. Exception. Where the entire project is constructed in compliance with the current Insurance Institute for Business & Home Safety (IBHS) Wildfire Technical Standards, the required fire flow may comply with the standard fire-flow requirements of Appendix B without modification. (Ord. 626-25 § 1 (part), 2025)