§ 15.24.730 — NFPA 14, 2024 Edition

Murrieta Municipal Code (2026 S-23 through Ord. 639-26) · Murrieta Municipal Code § 15.24.730

Corpus is an independent public-information project, not the official City of Murrieta website. Stable reference: corpuslaw.us/code/2a1539b1-3270-4c68-9a96-6aae7728d985

15.24.730 NFPA 14, 2024 Edition.

NFPA 14, 2024 Edition, Installation of Standpipe and Hose Systems is hereby amended as follows: Section 9.5.1.1 is hereby deleted in its entirety and replaced as follows: 9.5.1.1 Class I and III Standpipe hose connections shall be unobstructed and shall be located not less than 18 inches or more than 24 inches above the finished floor. Class II Standpipe hose connections shall be unobstructed and shall be located not less than 3 feet or more than 5 feet above the finished floor. (Ord. 626-25 § 1 (part), 2025)