Sec. 13-185. - Gravity feed to burner.
(a) When to be used. Gravity feed shall be used only with burners arranged to prevent abnormal discharge of oil at the burner by automatic means specifically approved for the burner with which it is used. (b) Supply tanks. Gravity supply tanks shall not exceed two hundred seventy-five (275) gallons' individual capacity. Where more than one (1) gravity supply tank is permitted, such tanks shall be connected to the feed pipe leading to the burner through a manually operated, approved three-way valve in such a way that only one (1) tank can discharge its contents at one (1) time. (c) Level valve. Where oil is supplied to the burner by gravity and a constant level valve is not incorporated in the burner assembly or in an auxiliary tank used in connection with an automatic pump, an approved constant level valve shall be installed in the oil feed line at the gravity tank or as close thereto as practicable. The vent opening of such constant level valve shall be connected by piping or tubing to the outside of the building unless the constant level valve is provided with an antiflooding device. Vent pipes or tubing of constant level valves shall not be connected to tanks or tank vents.
(Code 1977, § 13-170)