For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 13-197 — Tests of tanks and piping

Code of Ordinances of the City of Hartford, Connecticut (Supp. No. 119: codified through Ordinance of May 11, 2026) · Hartford Code of Ordinances § 13-197

Corpus is an independent public-information project, not the official City of Hartford website. Stable reference: corpuslaw.us/code/27438ce0-4e2c-4a29-af63-69797ed42ed5

Sec. 13-197. - Tests of tanks and piping.

After installation and before being covered, tanks and piping shall be tested hydrostatically, or with equivalent air pressure, at a pressure not less than one and one-half (1½) times the maximum working pressure but not less than five (5) pounds per square inch at the highest point of the system. Instead of a pressure test, suction lines may be tested under a vacuum of not less than twenty (20) inches of mercury. Tests shall continue for at least thirty (30) minutes without a noticeable drop in pressure or vacuum.

(Code 1977, § 13-182)

Ask a question about Hartford law

Corpus searches the Hartford sections it holds and shows the ones that match, with their citations. Free, no sign-in.