§ 13-190 — Tank vents
Code of Ordinances of the City of Hartford, Connecticut (Supp. No. 119: codified through Ordinance of May 11, 2026) · Hartford Code of Ordinances § 13-190
Corpus is an independent public-information project, not the official City of Hartford website. Stable reference: corpuslaw.us/code/60a99a62-3dcf-4496-9726-bd2dea17110b
Sec. 13-190. - Tank vents.
(a) Storage tanks shall be equipped with an open vent or an approved automatic vent arranged to discharge to the open air. Vent openings and vent pipes shall be of ample size to prevent abnormal pressure in the tank during filling, but not smaller than a one-and-one-quarter-inch size. (b) Vent pipes shall be arranged to drain to the tank. The lower end of the vent pipe shall not extend through the top into the tank for a distance of more than one (1) inch. (c) Vent pipes shall terminate outside of buildings at a point not less than two (2) feet, measured vertically or horizontally, from any window or other building opening. Outer ends of vent pipes shall be provided with a weatherproof hood. Vent pipes shall terminate sufficiently above the ground to prevent their being obstructed with snow and ice. Vent pipes of tanks containing heaters shall be extended to such a height that oil vapors discharging from the vent will be readily diffused without danger of ignition. (d) Vent pipes shall not be cross-connected with fill pipes or return lines from burners.
(Code 1977, § 13-175)