Sec. 13-188. - Installation of tanks inside buildings.
(a) Oil supply tanks larger than sixty (60) gallons in capacity shall not be located in buildings above the lowest story, cellar or basement. (b) Unenclosed inside storage tanks and auxiliary tanks shall not be located within seven (7) feet, horizontally, of any fire or flame. (c) Inside storage and auxiliary tanks shall be securely supported by substantial, incombustible supports to prevent settling, sliding or lifting. (d) Oil supply tanks located inside buildings shall not exceed two hundred seventy-five (275) gallons' individual capacity or five hundred fifty (550) gallons aggregate capacity in one (1) building unless installed in an enclosure or casing constructed as follows: The walls of the enclosure shall be constructed of reinforced concrete at least six (6) inches thick or of brick at least eight (8) inches thick and shall be bonded to the floor. The space between the tank and the enclosure shall be completely filled with sand or well-tamped earth. Where the floor or other construction immediately above the tank is of fire-resistive construction capable of sustaining safely a load of one hundred fifty (150) pounds per square foot, the walls of the enclosure shall be carried to a height of not less than one (1) foot above the tank, and the space filled with sand or well-tamped earth to the top; otherwise the enclosure shall have a top of reinforced concrete at least five (5) inches thick or of equivalent construction. Instead of an enclosure as above described, the tank may be encased in reinforced concrete not less than six (6) inches thick applied directly to the tank so as to eliminate completely any air space. Tanks of reinforced concrete construction as provided in section 13-189 may be installed without additional concrete enclosure. (e) In ordinary buildings, the nominal gross capacity of tanks shall not exceed five thousand (5,000) gallons. (f) In fire-resistive buildings, the nominal gross capacity of tanks shall not exceed fifteen thousand (15,000) gallons. (g) In any building, if in a fire-resistive or detached room cut off vertically and horizontally in an approved manner from other floors of the main building, the nominal gross capacity of tanks shall not exceed fifty thousand (50,000) gallons with an individual tank capacity not exceeding twenty-five thousand (25,000) gallons.
(Code 1977, § 13-173)
Ask a question about Hartford law
Corpus searches the Hartford sections it holds and shows the ones that match, with their citations. Free, no sign-in.