Sec. 13-191. - Tank fill and overflow pipes.

(a) Underground and storage tanks inside buildings shall be filled only through fill pipes terminating outside of buildings at a point at least five (5) feet from any building opening at the same or lower level. Fill terminals shall be closed tight when not in use by a metal cover designed to prevent tampering. (b) Auxiliary tanks shall be filled by pump from storage tanks. (c) Auxiliary tanks other than vacuum tanks shall be equipped with an overflow pipe draining to the storage tank at least one (1) size larger than the supply pipe. (d) Overflow pipes of auxiliary gravity tanks shall have no valves or obstructions. Overflow pipes of auxiliary pressure tanks shall be provided with interconnected valves or other means for automatically venting the tank during filling.

(Code 1977, § 13-176)