Sec. 13-189. - Construction of tanks.

(a) Underground tanks and tanks inside buildings shall be constructed of steel or wrought iron of a minimum U.S. standard gauge in accordance with the following table. Steel or wrought iron thinner than No. 7 gauge used in the construction of underground and enclosed tanks shall be galvanized. Capacity gallons | Minimum thickness | Weight pounds per square foot 180 or less | 16 guage | 2.50 181 to 285 | 14 guage | 3.125 286 to 1,100 | 12 guage | 4.375 1,101 to 4,000 | 7 guage | 7.50 4,001 to 12,000 | ¼ inch (nominal) | 10.00 12,001 to 20,000 | 5/16 inch (nominal) | 12.50 20,001 to 30,000 | ⅜ inch (nominal) | 15.00 If adequate internal bracing is provided, tanks of twelve thousand one (12,001) to thirty thousand (30,000) gallons' capacity may be built of one-quarter-inch plate. For tanks larger than one thousand one hundred (1,100) gallons' capacity, a tolerance of twenty (20) percent in capacity is permitted. (b) Joints shall be riveted, calked, brazed, welded or made tight by some equally satisfactory process. Tanks shall be tight and sufficiently strong to bear without injury the most severe strains to which they may be subjected in practice. Shells of tanks shall be properly reinforced where connections are made. All connections to underground tanks and tanks inside buildings shall be made through the top of the tank above the liquid level, except that tanks of not over two hundred seventy-five (275) gallons' capacity may have one (1) bottom connection for gravity feed and one (1) opening for an approved key stem gate valve to facilitate cleaning or for a scavenging line to be run to the outside and capped oiltight when not in use. (c) Pressure tanks shall be designed for at least six (6) times the maximum working pressure. (d) Prior to installation, underground and enclosed tanks shall be protected against corrosion on the outside in a manner satisfactory to the fire chief, but in every case by at least the equivalent to two (2) preliminary coatings of red lead followed by a heavy coating of hot asphalt. (e) Tanks labeled by Underwriters' Laboratories will be accepted as complying with the requirements of subsections (a) through (d). (f) For fuel oil heavier than thirty-five (35) degrees A.P.I., tanks may be made of concrete in accordance with the standards of the National Fire Protection Association for the design of concrete fuel oil storage tanks.

(Code 1977, § 13-174)

Ask a question about Hartford law

Corpus searches the Hartford sections it holds and shows the ones that match, with their citations. Free, no sign-in.