Sec. 13-187. - Installation of underground tanks.

(a) Underground tanks shall be so buried as to have a cover of earth not less than two (2) feet thick or shall be covered with not less than one (1) foot of earth on top of which shall be placed a slab of reinforced concrete not less than four (4) inches thick. The slab shall be set on a firm well-tamped earth foundation and shall extend at least one (1) foot beyond the tank in all directions. Where tanks are buried underneath buildings, such a concrete slab shall be provided in every instance. (b) Underground tanks shall be set on a firm foundation and surrounded with soft earth or sand, well tamped in place. Where necessary to prevent floating, they shall be securely anchored or weighted.

(Code 1977, § 13-172)