506.6. - SMOKE CONTROL.
(a) Natural or mechanical ventilation for the removal or control of products-of-combustion shall be provided in every story and shall consist of one or more of the following: 1. Panels or windows, in exterior walls. Such venting facilities shall be provided at the minimum rate of 2% of the exterior wall area in each story, and distributed around the perimeter at not more than fifty (50) foot intervals. Such panels or windows shall be clearly identified and shall have a minimum area of six square feet with at least a dimension of two (2) feet. 2. Approved tempered glass may be used in lieu of openable panels described above. 3. A continuous shaft or shafts through which smoke and heat can be mechanically vented to the outdoors. The size of any shaft shall be uniform throughout and of such dimension as to provide one (1) air change per minute in the largest compartment served by that shaft. Openings into shafts shall be protected with an automatic single piece shutter located as high in the room as possible and designed to vent the entire compartment. 4. The mechanical air handling equipment may be designed to direct return and exhaust air directly to the outdoors under fire conditions. 5. Any other approved design which will produce equivalent results. (b) Exit stairways shall be mechanically pressurized during a fire situation to 0.15 inches of water column minimum differential pressure across any closed stairway door with outside air in a manner approved by the Director. The maximum degree of pressurization shall be such that the opening of stairway doors can be accomplished with a force not to exceed twenty-five (25) pounds applied at the door knob. Additionally, the pressurization system shall be designed with assumption that during a fire situation the following doors are open: the fire door, adjacent doors above and below the fire floor, and the door of exit discharge from the shaft; and the minimum velocity through the four opened doors shall be no less than 150 feet per minute. (c) Elevator shafts shall be protected in a manner approved by the Director to prevent the entry of smoke or other products of combustion, or shall be pressurized to 0.10 minimum to 0.20 maximum inches of water column differential pressure across any elevator door in a manner approved by the Director. (d) Required ventilation of shafts as set forth in other sections of this code may be modified by approved means where tempered outside air is required for the pressurization of such shafts. Also, approved motorized dampers, signalled by smoke/ionization detectors, may be used to effect the necessary control of required pressurization. (e) Activation of all pressurization system shall occur due to response of: any smoke/ionization detector, manual fire alarm system, and sprinkler flow detector if installed. Means for deactivation of the pressurization system shall be provided in the Central Control Station. Additionally, the design of the pressurization system shall insure that no smoke be introduced in the shaft as a result of contamination of the fresh air intake(s). (f) It shall be the responsibility of the architect, or a designated agent, to submit a comprehensive written description of all systems that are installed as a result of this subsection. Copies of this report shall be submitted to the City of Atlanta, Bureau of Fire Services and the City of Atlanta, Bureau of Buildings, as well as being permanently posted in the Central Control Station. Pressurization Commentary: 1. Weather conditions may require special consideration in stair and elevator shaft pressurization designs. It may be necessary to introduce outside air heated to approximately the same temperature as is maintained in the building in order to limit pressures within the shafts to the range of pressures required by this subsection. 2. Stack effect in high rise buildings will make permanently opened louvers in the top of stair and elevator shafts undesirable because of loss of heated air. 3. Relative to stairway pressurization, reference should be made to the ASHRAE Guides or other appropriate data for door leakage values in order to facilitate design. However, it is noted for information purposes that full scale testing has indicated that leakages of approximately 200 cfm per door are representative, and that the propeller type fan having a characteristic fan performance curve of high volume/low pressure has been found to produce desired results.
Ask a question about Atlanta law
Corpus searches the Atlanta sections it holds and shows the ones that match, with their citations. Free, no sign-in.