506.8. - MODIFICATIONS.
When an approved, supervised, sprinkler system is installed in accordance with subsection 506.2, the following modifications to this code are permitted: (a) The fire resistance rating of shafts, other than exitway stairway and elevator enclosure shafts, may be reduced to one (1) hour. (b) The fire resistance rating of partitions separating dwelling units from corridors and other occupancies in multifamily houses may be reduced to one-half (½) hour. (c) The fire protection rating of corridor doors from guest rooms in hotels and dwelling units in multifamily houses may be reduced to twenty (20) minutes. Approved one and three-quarter (1¾) inch solid bonded wood core doors of the flush type may be accepted. However, all such doors opening into a public corridor shall be equipped with approved door closers. (d) A class I or Class III Standpipe shall be provided.